Norgren VP51 DeviceNet Installation Instructions Manual de usuario Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 11
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
4
5. INSTALLATION
Pneumatic Installation
Supply Pressure: 15psig above maximum output required
(200psig max.)
Output Pressure Range: 0-150psig
Media: clean, dry 50µ filtered air
Porting: G1/4; 1/4NPT; ISO2 Manifold Mount
Use oil-free air
Do not use PTFE tape
G1/4 & 1/4NPT variants
Electrical
connector
Return spring
housing.
Do not
adjust.
Exhaust port (3
)
Supply port
(1)
Output port (2)
1
3
2
Connect pipe-work using 10mm OD, 8mm ID, plastic pipe, cut cleanly at right angles, with push-fit pipe
connections.
Fit an exhaust silencer to Port 3 if required (this will only slightly degrade exhaust performance)
ISO2 Manifold Mount variant
Electrical
connector
Return spring
housing.
Do not
adjust.
Exhaust port (3
)
Supply port
(1)
Output port (2)
Output port (2)
Exhaust port (3)
Supply port (1)
ISO-2 sub base
mounting holes
VP51 mounting holes
(M4 tapped) x 2
Use grub screws provided to plug cross drilled holes in interface plate
Mount interface plate to ISO-2 sub base with four M6 screws, with gasket between plate and sub base.
Place three O-rings in three counterbored holes in plate and mount VP51 with two M4 screws.
Electrical Installation
Connect the unit as follows using DeviceNet approved screened cable and a M12 female connector or with a
ready made M12 DeviceNet cable:
1
2
4
5
3
Connector pinout
looking onto the end of
the instrument
Pin 1: Drain (bare)
Pin 2: V+ (red)
Pin 3: V- (black)
Pin 4: CAN_H (white)
Pin 5: CAN_L (blue)